Product Description
Summarize
:
CSM-SL3 is an upgrade of the traditional fault , indicator not only inherited the advantages of traditional fault indicator, also made two major improvements:
1.
Increasing monochrome LCD, it can real-time display current three-phase operation,
zero sequence current, cable temperature, ambient temperature,
2.
Ground current, short-circuit current threshold can be modified by the panel menu button and set the threshold.
Features
Δ
Digital design, dot matrix LCD display
Δ
With four function buttons, menus detailed and easy to operate
Δ
Synchronous display phase current, ground current value
Δ
Synchronous display three-phase' cable operating temperature (optional)
Δ
Built-in real time clock
Δ
LCD has battery power display, the battery easy to replace
Δ
Sensors build-in the CPU, which dealt with the data is accurately
Δ
Optical transmission, safe and reliable
Δ
Provide 485 communication interface, can connect to internet and remote data (optional)
Δ
Users can on-site or remote set current and temperature alarm thresholds and alarm display time
Δ
Can be stored, check alarm events (including time, sources of information, the current value and so on)
Δ
Provide remote alarm output and reset interfaces
Technical parameters
Short circuit fault current:
1A ~ 1500A
Ground current:
1A ~ 200 A
Reset delay time:
1S ~ 99H
Over-temperature alarm:
0
ºC
~ 150
ºC
Host Operate temp display:
40
ºC
~ 105
ºC
Static power consumption:
≤5uA
Maximum power alarm:
≤6mA
Power Supply:
DC 5V
,
DC 24V
,
AC 110V-220V
,
3.6V
,
Lithium Battery