Summarize:
The current temperature fault online indicator CSM-SL3-I not only has traditional short circuit and ground fault warning function, also has real-time monitoring of the load current and temperature parameters, and has 485 interface, which can connect DTU Data Remote. CSM-SL3-I is the creative design of Distribution network terminals inferred from the digital application and achieve the Grid standard IEC60870-5-101 Statute, with the Master background's good compatibility and docking, it optimizes distribution automation RTU solutions, that will push the intelligent distribution automation.
Features
Δ High-precision color LCD screen displays the current temperature and switch barometer state real-time
Δ Cables temperature, current monitoring, and accident prevention in the first place
Δ High-precision sensors, the accuracy current measurement accuracy meets distribution automation requirements
Δ Fault monitoring with the trip recognition, completely solve the problem of a ground fault misjudgment
Δ Low-power design, to adapt to a variety of power supply
Technical parameters
Short circuit fault current: 1A-1500A can be set(Default:800A)
Overheating alarm temperature:1ºC-150ºC can be set(Default:70ºC)
The ground fault current:1A-200A can be set(Default:40A)
The detection range of the phase line current:0A-1500A
The detection range of the phase line temperature:-20ºC~150ºC
The detection range of the ground current detection range:0A-200A
Reset time:1S-99H (Default:24H)
Working power:
1,The external power supply optional:DC5V,DC24V,DC48V,AC220V
2,Rechargeable lithium battery3.6V /750mAH Protection level:IP65
Power consumption:
Normal working mode power consumption:3.6V Lithium battery-powered≤1mA
Alarm mode power consumption:3.6V Lithium battery-powered≤6mA
Communication mode power consumption:3.6V Lithium battery-powered≤10mA
Environmental conditions:
Operating Altitude:≤1000m
Working environment temperature: -40ºC~+70ºC
Maximum temperature head:25ºC
Working environment humidity:≤95% (Relative humidity)
Seismic capacity:
Seismic intensity: 8
Safety factor: 1.67
Ground horizontal acceleration:0.3g
Perpendicular to the ground acceleration:0.15g
Normal work under condensation and salt spray corrosion conditions which lasted for three sine wave
Running conditions and mounting position:Indoor or outdoor box, installed in the 0.4 ~ 35kV cable itself.
Neutral grounding:The Net Neutral through low resistance grounding or arc suppression coil grounding.